Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/23040
Título : A communication-free reactive-power control strategy in VSC-HVDC multi-terminal systems to improve transient stability
Autor : Renedo Anglada, Javier
Rouco Rodríguez, Luis
García Cerrada, Aurelio
Sigrist, Lukas
Resumen : 
This paper proposes a new reactive-power control strategy for High Voltage Direct Current multi-terminal systems with Voltage Source Converter stations (VSC-HVDC) to improve transient stability in electric power transmission systems. The proposed algorithm uses local measurements to estimate, in each converter station, a weighted average of the frequencies seen by the VSC stations of the HVDC multi-terminal system. This estimation is carried out making use of a (small) auxiliary local active-power modulation along with the DC-side voltage droop control in the VSC stations, where the latter also uses local measurements only. The estimated frequency is used as the set point for supplementary reactive-power control at each converter station. The proposed control law has been simulated in a test system using PSSE and the results show that it improves transient stability, significantly, producing similar results to those obtained controlling reactive power using global measurements.
URI : http://hdl.handle.net/11531/23040
Aparece en las colecciones: Documentos de Trabajo

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
IIT-17-005A.pdf1,66 MBAdobe PDFVisualizar/Abrir


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.