Título : | Open phase faults in the start-up power supply system of a nuclear power generating station |
Autor : | Rouco Rodríguez, Luis Archilla Martín-Sanz, Jacobo Gavilán Moreno, Carlos |
Resumen : | This paper investigates whether existing protection schemes would detect an open phase fault in the start-up power supply system of a 1092 MW Spanish nuclear power generating station. This investigation follows to the 2012 event at unit 2 of Byron station, Illinois, USA. Symmetrical components method is proposed to draw fundamental conclusions. The results of the symmetrical components analysis are validated using EMTP simulations. |