Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/40644
Título : Open phase faults in the start-up power supply system of a nuclear power generating station
Autor : Rouco Rodríguez, Luis
Archilla Martín-Sanz, Jacobo
Gavilán Moreno, Carlos
Resumen : 
This paper investigates whether existing protection schemes would detect an open phase fault in the start-up power supply system of a 1092 MW Spanish nuclear power generating station. This investigation follows to the 2012 event at unit 2 of Byron station, Illinois, USA. Symmetrical components method is proposed to draw fundamental conclusions. The results of the symmetrical components analysis are validated using EMTP simulations.
URI : http://hdl.handle.net/11531/40644
Aparece en las colecciones: Documentos de Trabajo