Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/96443
Título : Remote open phase faults in the start-up transformers of a nuclear power generating station
Autor : Rouco Rodríguez, Luis
Archilla Martín-Sanz, Jacobo
Gavilán Moreno, Carlos
Resumen : 
United States Nuclear Regulatory Commission (US NRC) has requested to the US nuclear power generating industry that Open Phase Conditions (OPCs) should be automatically detected. This requirement has been extended by other regulatory bodies worldwide. Several systems for detecting OPCs are available in the marketplace. Remote open phase faults in the supply system of start-up transformers of nuclear power generating stations (NPGSs) pose a major challenge for available detection systems. A remote fault consists of an open phase fault in an intermediate point of the transmission line that feeds the startup transformer of the NPGS. This paper investigates the ability of existing methods to detect a remote open phase fault in the transmission line that feeds the start-up transformer of a NPGS.
URI : http://hdl.handle.net/11531/96443
Aparece en las colecciones: Documentos de Trabajo

Ficheros en este ítem:
Fichero Tamaño Formato  
IIT-22-115C.pdf393,17 kBAdobe PDFVisualizar/Abrir     Request a copy


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.