Renedo Anglada, Javier
Rouco Rodríguez, Luis
Sigrist, Lukas
García Cerrada, Aurelio
2020-05-01T03:15:24Z
2020-05-01T03:15:24Z
2019-10-14
http://hdl.handle.net/11531/46045
Capítulos en libros
This paper presents a fundamental study on the impact of AC-line-emulation controllers of High Voltage Direct Current links based on Voltage Source Converters (VSC-HVDC) on inter-area-oscillation damping. The analysis has been carried out using eigenvalue and frequency-domain methods. The results presented in the paper show that an AC-line-emulation controller in a VSC-HVDC link can have either a positive or negative impact on the damping ratio of inter-area modes, depending on the value of the filter time constant of the controller. The study concludes that the filter time constant must be high enough to avoid negative interactions of this control alternative on power oscillations and the paper provides guidelines for the design of this parameter.
application/pdf
en-GB
IEEE Industrial Electronics Society; Institute of Electrical and Electronics Engineers (Lisboa, Portugal)
Libro: 45th Annual Conference of the IEEE Industrial Electronics Society - IECON 2019, Página inicial: 4825-4830, Página final:
Instituto de Investigación Tecnológica (IIT)
Impact of AC-line-emulation controllers of VSC-HVDC links on inter-area-oscillation damping
info:eu-repo/semantics/bookPart
info:eu-repo/semantics/publishedVersion
info:eu-repo/semantics/restrictedAccess
HVDC transmission, VSC-HVDC, AC line emulation control, power oscillation damping, power system stability.