• English
    • español
  • español 
    • English
    • español
  • Login
Ver ítem 
  •   DSpace Principal
  • 2.- Investigación
  • Artículos
  • Ver ítem
  •   DSpace Principal
  • 2.- Investigación
  • Artículos
  • Ver ítem
JavaScript is disabled for your browser. Some features of this site may not work without it.

Influence of atrium roof geometries on the numerical predictions of fire tests under natural ventilation conditions

Thumbnail
Ver/
ENB_2013_preprint.pdf (7.737Mb)
Fecha
2013-10-01
Autor
Ayala Santamaría, Pablo
Cantizano González, Alexis
Gutiérrez Montes, Cándido
Rein Soto-Yarritu, Guillermo
Estado
info:eu-repo/semantics/publishedVersion
Metadatos
Mostrar el registro completo del ítem
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Resumen
 
 
The use of computational fluid dynamics (CFD) as a tool for the design of smoke control systems and fire protection in large spaces has become more frequent as accuracy and computational speeds increase. In the present work Fire Dynamic Simulator (FDSv5) has been used to study two full-scale experiments conducted in Murcia (Spain) of 1.36 MW and 2.34 MW pool fires burning inside a 20 m cubic atrium under natural ventilation conditions. Different cartesian-grid approximations to the real geometry of the pyramidal roof have been investigated in order to assess the effect of stair stepping on the smoke layer and the temperature field. In general terms, good agreement between experiments and numerical simulations is found for all model roof geometries, especially far away from the fire source and the centreline. For example, at a height of 15 m, the temperature differences between all geometry approximations are lower than 10. This shows that the cartesian-grid simplifications proposed here are a good choice and allow for saving some computational resources. In order to extend the results to different designs, the model has then been applied to study a range of 16 different atrium geometries, varying the area-to-height-squared ratio from 0.4 to 3.8. In addition, a comparison with simulation with a previous version of the code, FDSv4, shows that it predicts higher temperatures and slower ascends of the smoke layer than FDSv5, the difference being lower than 12 and 100 s respectively.
 
URI
https:doi.org10.1016j.enbuild.2013.06.010
Influence of atrium roof geometries on the numerical predictions of fire tests under natural ventilation conditions
Tipo de Actividad
Artículos en revistas
ISSN
0378-7788
Materias/ categorías / ODS
Instituto de Investigación Tecnológica (IIT)
Palabras Clave

Atrium; Full scale fire tests; Smoke; CFD simulations; FDSv5; FDSv4
Colecciones
  • Artículos

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contacto | Sugerencias
 

 

Búsqueda semántica (CKH Explorer)


Listar

Todo DSpaceComunidades & ColeccionesPor fecha de publicaciónAutoresTítulosMateriasPor DirectorPor tipoEsta colecciónPor fecha de publicaciónAutoresTítulosMateriasPor DirectorPor tipo

Mi cuenta

AccederRegistro

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contacto | Sugerencias