dc.contributor.authorGarcía Cerrada, Aurelioes-ES
dc.contributor.authorPinzón Ardila, Omares-ES
dc.contributor.authorFeliú Batlle, Vicentees-ES
dc.contributor.authorRoncero Sánchez-Elipe, Pedro Luises-ES
dc.contributor.authorGarcía González, Pabloes-ES
dc.date.accessioned2016-01-15T11:19:20Z
dc.date.available2016-01-15T11:19:20Z
dc.date.issued2007-01-01es_ES
dc.identifier.issn0885-8993es_ES
dc.identifier.urihttps:doi.org10.1109TPEL.2006.886609es_ES
dc.descriptionArtículos en revistases_ES
dc.description.abstractes-ES
dc.description.abstractThis paper presents the detailed design, analysis, and application of the controller for a shunt active power filter based on a pulsewidth modulation dc-to-ac voltage source converter. The controller is mainly tailored to compensate harmonic currents of nonlinear loads connected to the mains. However, it can also achieve reactive-power compensation and mains-current balancing when required. The controller has a two-layer structure. The outer layer generates the current references for the inner layer. The former uses a plug-in discrete-time repetitive algorithm for current-harmonic compensation, a proportional–integral algorithm to maintain the dc-capacitor voltage in spite of unmodeled losses and a reactive-power-reference generator. The inner layer uses state-feedback with integral action for current control. The repetitive controller is justified to improve the tracking of the periodic current references required by the active filters. The stability of the resulting closed-loop system is studied and some indication of the system robustness is given. The proposed controller has been tested in a prototype with balanced and unbalanced nonlinear loads. A discrete-time model of the filter has been used from the beginning. The microcomputer delay when calculating the controller output and the delay due to the anti-aliasing filters have been included in the inner system state-variable model.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.uries_ES
dc.sourceRevista: IEEE Transactions on Power Electronics, Periodo: 1, Volumen: online, Número: 1, Página inicial: 237, Página final: 246es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titleApplication of a repetitive controller for a three-phase active power filteres_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.accessRightsinfo:eu-repo/semantics/restrictedAccesses_ES
dc.keywordses-ES
dc.keywordsActive power filters (APFs), dc-to-ac electronic converters, power quality, repetitive controlen-GB