Optimal power flow operation of an interline current flow controller in an hybrid ACDC meshed grid
dc.contributor.author | Sau Bassols, Joan | es-ES |
dc.contributor.author | Zhao, Quanyu | es-ES |
dc.contributor.author | García González, Javier | es-ES |
dc.contributor.author | Prieto Araujo, Eduardo | es-ES |
dc.contributor.author | Gomis Bellmunt, Oriol | es-ES |
dc.date.accessioned | 2019-11-27T04:15:52Z | |
dc.date.available | 2019-11-27T04:15:52Z | |
dc.date.issued | 2019-12-01 | es_ES |
dc.identifier.issn | 0378-7796 | es_ES |
dc.identifier.uri | https:doi.org10.1016j.epsr.2019.105935 | es_ES |
dc.description | Artículos en revistas | es_ES |
dc.description.abstract | es-ES | |
dc.description.abstract | This paper is meant to show that an interline current flow controller (CFC) is able to reduce the operating costs of hybrid ACDC meshed grids by alleviating the congestion within the DC lines. The work considers a unidirectional DCDC CFC with a simple structure and its average model is introduced into the mathematical formulation of the Optimal Power Flow (OPF) problem of an hybrid ACDC meshed grid, which also considers the losses of the Voltage Source Converters (VSC). The CFC restrictions and the different connection arrangements of the device into the ACDC grid are also included in the model and show an important effect on the OPF solution. The case studies are conducted in a 5-terminal ACDC meshed grid and point out that the CFC has a reduced capability to reduce the operating costs of the system if there are no overloads in the DC lines. However, when the power limit of one of the lines is reached, the CFC can redirect part of the DC current and, therefore, reduce the operating costs compared to the case without CFC. | en-GB |
dc.format.mimetype | application/pdf | es_ES |
dc.language.iso | en-GB | es_ES |
dc.rights | es_ES | |
dc.rights.uri | es_ES | |
dc.source | Revista: Electric Power Systems Research, Periodo: 1, Volumen: online, Número: , Página inicial: 105935-1, Página final: 105935-9 | es_ES |
dc.subject.other | Instituto de Investigación Tecnológica (IIT) | es_ES |
dc.title | Optimal power flow operation of an interline current flow controller in an hybrid ACDC meshed grid | es_ES |
dc.type | info:eu-repo/semantics/article | es_ES |
dc.description.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.rights.accessRights | info:eu-repo/semantics/restrictedAccess | es_ES |
dc.keywords | es-ES | |
dc.keywords | Optimal power flow; Current flow controller; Meshed ACDC grid; Cost minimization | en-GB |
dc.identifier.doi | 10.1016/j.epsr.2019.105935 | es_ES |
Ficheros en el ítem
Este ítem aparece en la(s) siguiente(s) colección(ones)
-
Artículos