Protection of power transformers connected to gis against lightning overvoltages

Thumbnail
View/Open
IIT-14-091A.pdf (597.5Kb)
Date
2014-08-24
Author
Rouco Rodríguez, Luis
Sigrist, Lukas
Gago García, Hugo
Palazuelos Bertó, Emilio
Bernal López, Jesús
Jimeno, M.A.
Estado
info:eu-repo/semantics/publishedVersion
Metadata
Show full item record
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Abstract
 
 
During the last ten years Iberdrola Distribución Eléctrica has built a considerable number of high voltagemedium voltage transformer stations in urban areas using high voltage (220 kV and 132 kV) Gas Insulated Substations (GISs). The typical configuration of such GISs is double bar with two transmission line bays, two transformer bays and a coupling bay. Overhead transmission lines and power transformers are connected to the GIS using either insulated cables or Gas Insulated Lines (GILs) of different length. The protection of the power transformers against lightning overvoltages is performed with surge arresters at the connection point of the overhead lines with either the insulated cables or the GILs. This paper reports an exhaustive study conducted by Iberdrola aimed at assessing the performance of the protective scheme in three configurations in both 132 kV and 220 kV stations: 1. Power transformers are connected to the GIS using GILSs. Overhead lines are connected to the GIS also using GILs. 2. Power transformers are connected to the GIS using insulated cables. Overhead lines are connected to the GIS also using insulated cables. 3. Power transformers are connected to the GIS using insulated cables. Overhead lines are connected to the GIS using GILs. Very detailed models of the stations for electromagnetic transient simulation have been developed using manufacturer data of the GISs, insulated cables, GILs, power transformers and surge arresters. The study has comprised simulation of a reference case of each configuration and several sensitivity studies with respect to the length of the insulated cables and the GILs.
 
URI
http://hdl.handle.net/11531/5473
Protection of power transformers connected to gis against lightning overvoltages
Tipo de Actividad
Capítulos en libros
Materias/ categorías / ODS
Instituto de Investigación Tecnológica (IIT)
Palabras Clave

Transformer stations, Gas Insulated Substations, Insulated cables, Gas Insulated Lines, Lightning overvoltages, Electromagnetic transient simulation
Collections
  • Artículos

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback
 

 

Búsqueda semántica (CKH Explorer)


Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_typeThis CollectionBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_type

My Account

LoginRegister

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback