Fault location method based on the determination of the minimum fault reactance for uncertainty loaded and unbalanced power distribution systems

Thumbnail
View/Open
IIT-11-082A.pdf (467.0Kb)
Date
2010-11-08
Author
Morales España, German Andres
Mora Flórez, Juan
Vargas Torres, Hermann Raúl
Estado
info:eu-repo/semantics/publishedVersion
Metadata
Show full item record
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Abstract
 
 
One of the widely recognized and most important aspects of power quality is related to power continuity. The fault location in power distribution systems is normally a not simple task, considering the complexity associated to these circuits due to several characteristics such as single end measurements, the presence of different conductors and line configurations, uncertain load distribution, presence of single phase laterals, system and load unbalances, among others. In this paper, a novel fault location method is proposed considering the above mentioned characteristics. This method is based on a iterative approach to determine the minimum fault reactance and uses the line series impedance matrix, measurements of prefault and fault voltages and currents at the power substation. The performance of the proposed algorithm is here evaluated by an application example in a power distribution system, commonly referenced in fault location papers. The tests are performed considering several fault situations and including a sensibility analysis for load variations. As result, the absolute error in distance estimation, is lower than 3.5.
 
URI
http://hdl.handle.net/11531/5586
Fault location method based on the determination of the minimum fault reactance for uncertainty loaded and unbalanced power distribution systems
Tipo de Actividad
Capítulos en libros
Materias/ categorías / ODS
Instituto de Investigación Tecnológica (IIT)
Palabras Clave

Fault location, fault reactance, power distribution systems, power quality, service continuity indexes, uncertain load distribution
Collections
  • Artículos

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback
 

 

Búsqueda semántica (CKH Explorer)


Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_typeThis CollectionBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_type

My Account

LoginRegister

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback