Mostrar el registro sencillo del ítem

dc.contributor.authorSeyedmahdi, Izadkhastes-ES
dc.contributor.authorCossent Arín, Rafaeles-ES
dc.contributor.authorFrías Marín, Pabloes-ES
dc.contributor.authorGarcía González, Pabloes-ES
dc.contributor.authorRodríguez Calvo, Andreaes-ES
dc.date.accessioned2022-03-22T17:34:54Z
dc.date.available2022-03-22T17:34:54Z
dc.date.issued2022-03-01es_ES
dc.identifier.issn1996-1073es_ES
dc.identifier.urihttps:doi.org10.3390en15051736es_ES
dc.descriptionArtículos en revistases_ES
dc.description.abstractes-ES
dc.description.abstractThe main purpose of this paper is to evaluate the overall performance of a battery energy storage system (BESS) during (I) grid-connected, (II) black start, and (III) islanded operating modes. To do so, firstly, a novel three-mode controller is proposed and developed. The proportional–integral–derivative (PID) controller is implemented, including the following three components: (1) inertia emulation, (2) frequency-active power and voltage-reactive power droops, and (3) secondary frequency and voltage controllers. Secondly, to effectively evaluate the proposed controller performance under various grid operating conditions during both black start and seamless transition to islanded operation, a set of comprehensive dynamic simulations using MatlabSimulink is carried out. To this end, the sensitivity analyses on numerous grid operating parameters, such as pre-disturbance grid power, total installed BESS capacity, battery state of charge, unbalanced three-phase load flows, implemented power-frequency controller parameters, and distribution network types with various shares of dynamic and static loads, are performed. Thirdly, to practically improve the seamless transition performance enabling the demand response participation, a fast-controlled thermostatic load scheme is implemented. Simulation results show that the BESS unit using the proposed three-mode controller has great potential to successfully control the frequency and voltage within allowable limits during both islanding and black start modes over a wide range of grid operating conditions.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.sourceRevista: Energies, Periodo: 1, Volumen: online, Número: 5, Página inicial: 1736-1, Página final: 1736-21es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titlePerformance evaluation of a BESS unit for black start and seamless islanding operationes_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.holderes_ES
dc.rights.accessRightsinfo:eu-repo/semantics/openAccesses_ES
dc.keywordses-ES
dc.keywordsbattery energy storage system; black start; islanding; power distribution; three-mode controlleren-GB


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(ones)

  • Artículos
    Artículos de revista, capítulos de libro y contribuciones en congresos publicadas.

Mostrar el registro sencillo del ítem