Sizing of a battery energy storage system to minimize underfrecuency load shedding in island power systems

dc.contributor.authorSigrist, Lukases-ES
dc.contributor.authorRouco Rodríguez, Luises-ES
dc.contributor.authorJiménez Serrano, Claraes-ES
dc.date.accessioned2019-05-23T03:11:50Z
dc.date.available2019-05-23T03:11:50Z
dc.description.abstractes-ES
dc.description.abstractThis paper presents a method to size battery energy storage systems (BESSs) to minimize underfrequency load shedding in island power systems. The proposed method depends on a simplified representation of the power system, where generating units are represented by firstorder systems. An analytical expression is derived to estimate the BESS size. The proposed method has been applied to two Spanish isolated power systems. Dynamic simulations with PSS/E software package confirm the proposed method to size BESS. BESS with a capacity around 6% to 9% of the installed generation capacity are needed to avoid load shedding.en-GB
dc.description.versioninfo:eu-repo/semantics/draftes_ES
dc.format.mimetypeapplication/pdfes_ES
dc.identifier.urihttp://hdl.handle.net/11531/36855
dc.keywordses-ES
dc.keywordsen-GB
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.accessRightsinfo:eu-repo/semantics/openAccesses_ES
dc.rights.holderes_ES
dc.rights.uries_ES
dc.titleSizing of a battery energy storage system to minimize underfrecuency load shedding in island power systemses_ES
dc.typeinfo:eu-repo/semantics/workingPaperes_ES

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
IIT-19-044A.pdf
Size:
953.19 KB
Format:
Adobe Portable Document Format