On the Use of a Convex Model for Bulk Storage in MIP-Based Power System Operation and Planning

dc.contributor.authorArroyo, José M.es-ES
dc.contributor.authorBaringo Morales, Luises-ES
dc.contributor.authorBaringo Morales, Anaes-ES
dc.contributor.authorBolaños, Ricardoes-ES
dc.contributor.authorAlguacil Conde, Nataliaes-ES
dc.contributor.authorCobos, Noemi G.es-ES
dc.date.accessioned2023-07-24T12:28:43Z
dc.date.available2023-07-24T12:28:43Z
dc.date.issued2020-11-01es_ES
dc.descriptionArtículos en revistases_ES
dc.description.abstract.es-ES
dc.description.abstractRecently, several authors have reported specific criteria to support the widely accepted use of a convex operational model for bulk energy storage in the formulation of power system operation and planning problems involving binary variables. Using two counterexamples, we show that this modeling simplification may give rise to impractical solutions featuring simultaneous charging and discharging, even though the recently published criteria are satisfied. Thus, both counterexamples invalidate those criteria and demonstrate that the customarily used convex model may be unsuitable for the precise incorporation of bulk storage in such instances of mixed-integer programming.en-GB
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.format.mimetypeapplication/pdfes_ES
dc.identifier.issn0885-8950es_ES
dc.identifier.uri10.1109/TPWRS.2020.3020730es_ES
dc.identifier.urihttp://hdl.handle.net/11531/81118
dc.keywords.es-ES
dc.keywords—Convex operational model, electrical energy storage, power system operation and planning with binary variables, simultaneous charging and discharging.en-GB
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.accessRightsinfo:eu-repo/semantics/restrictedAccesses_ES
dc.rights.holderLa editorial no permite el depósito en abiertoes_ES
dc.rights.uries_ES
dc.sourceRevista: IEEE Transactions on Power Systems, Periodo: 2, Volumen: 35, Número: 6, Página inicial: 4964, Página final: 4967es_ES
dc.titleOn the Use of a Convex Model for Bulk Storage in MIP-Based Power System Operation and Planninges_ES