Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/100539
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.authorSuárez Porras, Jorgees-ES
dc.contributor.authorFernández Bernal, Fideles-ES
dc.contributor.authorRouco Rodríguez, Luises-ES
dc.contributor.authorTomás Martín, Andréses-ES
dc.date.accessioned2025-07-10T14:19:51Z-
dc.date.available2025-07-10T14:19:51Z-
dc.date.issued2025-06-09es_ES
dc.identifier.issn0885-8969es_ES
dc.identifier.urihttps:doi.org10.1109TEC.2025.3578132es_ES
dc.identifier.urihttp://hdl.handle.net/11531/100539-
dc.descriptionArtículos en revistases_ES
dc.description.abstractes-ES
dc.description.abstractThis paper examines the impact of Synchronous Compensators (SC) on the stability of grid-following Inverter-Based Resources (IBRs), with a particular focus on the role of reactive power. Full-order simulation models of a commercial SC and a doubly-fed induction generator as the study model to represent the most complex IBR, are used. Using the short-circuit ratio (SCR) as the key index, the study confirms that the Phase-Locked Loop (PLL) in the IBR is crucial for system stability and shows that the reactive power injected by the SC plays a non-negligible role. It is shown that the main effect of the SC in the small-signal stability aspect is the Thévenin impedance seen by the PLL at the connection point, which, in the case of the SC, is the subtransient impedance and the SC reactive power. This idea is used to calculate the PLL eigenvalues movement easily. A new simple linear approximation model is proposed to estimate the correct SCR value for stability purposes considering the reactive power effect, as it is shown that the classical SCR measure does not fully capture the impact of the reactive power on the system stability.en-GB
dc.language.isoen-GBes_ES
dc.sourceRevista: IEEE Transactions on Energy Conversion, Periodo: 1, Volumen: En imprenta, Número: , Página inicial: 0, Página final: 0es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titleSynchronous Compensators Considering Reactive Power for PLL Stability Improvement and Short-Circuit Ratio Evaluationes_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.holderes_ES
dc.rights.accessRightsinfo:eu-repo/semantics/openAccesses_ES
dc.keywordses-ES
dc.keywordsSynchronous compensator, short-circuit ratio, reactive power, IBR stability, PLL stability.en-GB