Por favor, use este identificador para citar o enlazar este ítem:
http://hdl.handle.net/11531/108905| Título : | TDSF-Based Evaluation of Transformer Interactions with VCB, Cable Length, and Neutral Grounding |
| Autor : | Álvarez-Mariño, Casimiro López Fernández, Xosé Manuel Popov, Marjan Rouco Rodríguez, Luis |
| Fecha de publicación : | 26-nov-2025 |
| Editorial : | Universidade de Vigo (Bayona, España) |
| Resumen : | This paper presents a TDSF-based evaluation of dielectric severity in transformer windings, focusing on transient overvoltages induced by cable–transformer interactions during vacuum circuit breaker (VCB) closing. Unlike prior approaches limited to terminal voltages, this study investigates the highest both spatial and temporal dielectric stress across all combinations of winding nodes and their reference to ground. A hybrid white–black box transformer model implemented in ATP/EMTP is presented and used for high-frequency transient analysis within the transformer. Three case studies on a 50 MVA single-phase, multi-winding transformer validate the model and assess the impact of cable length and neutral grounding resistance. Results show that certain cable lengths increase dielectric stress due to resonance effects, though without exceeding critical thresholds. In contrast, grounding conditions at the LV terminal significantly affect the vulnerability of the winding neutral point. The findings underscore the effectiveness of TDSF-based evaluation in identifying critical stress locations and supporting insulation coordination strategies. This paper presents a TDSF-based evaluation of dielectric severity in transformer windings, focusing on transient overvoltages induced by cable–transformer interactions during vacuum circuit breaker (VCB) closing. Unlike prior approaches limited to terminal voltages, this study investigates the highest both spatial and temporal dielectric stress across all combinations of winding nodes and their reference to ground. A hybrid white–black box transformer model implemented in ATP/EMTP is presented and used for high-frequency transient analysis within the transformer. Three case studies on a 50 MVA single-phase, multi-winding transformer validate the model and assess the impact of cable length and neutral grounding resistance. Results show that certain cable lengths increase dielectric stress due to resonance effects, though without exceeding critical thresholds. In contrast, grounding conditions at the LV terminal significantly affect the vulnerability of the winding neutral point. The findings underscore the effectiveness of TDSF-based evaluation in identifying critical stress locations and supporting insulation coordination strategies. |
| Descripción : | Capítulos en libros |
| URI : | http://hdl.handle.net/11531/108905 |
| Aparece en las colecciones: | Artículos |
Ficheros en este ítem:
| Fichero | Tamaño | Formato | |
|---|---|---|---|
| IIT-25-408C.pdf | 1,41 MB | Adobe PDF | Visualizar/Abrir Request a copy |
Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.