Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/18059
Título : Economic viability of pumped-storage power plants equipped with ternary units and considering hydraulic short-circuit operation
Autor : Chazarra Jover, Manuel
Pérez-Díaz, Juan I.
García González, Javier
Fecha de publicación :  4
Resumen : 
This paper analyses the economic viability of pumped-storage hydropower plants equipped with ternary units and considering hydraulic short-circuit operation. The analysed plant is assumed to participate in the day-ahead energy market and in the secondary regulation service of the Spanish power system. A deterministic day-ahead energy and reserve scheduling model is used to estimate the maximum theoretical income of the plant assuming perfect information of the next day prices and the residual demand curves of the secondary regulation reserve market. Results show that the pay-back periods with and without the hydraulic short-circuit operation are significantly lower than their expected lifetime and that the pay-back periods can be reduced with the inclusion of the hydraulic short-circuit operation.
Descripción : Artículos en revistas
URI : http://hdl.handle.net/11531/18059
ISSN : 1742-6588
Aparece en las colecciones: Artículos

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
IIT-17-053A.pdf942,11 kBAdobe PDFVista previa
Visualizar/Abrir


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.