Por favor, use este identificador para citar o enlazar este ítem:
http://hdl.handle.net/11531/4812
Registro completo de metadatos
Campo DC | Valor | Lengua/Idioma |
---|---|---|
dc.contributor.author | Saboya Bautista, Inmaculada | es-ES |
dc.contributor.author | Egido Cortés, Ignacio | es-ES |
dc.contributor.author | Lobato Miguélez, Enrique | es-ES |
dc.date.accessioned | 2016-01-15T11:14:29Z | - |
dc.date.available | 2016-01-15T11:14:29Z | - |
dc.date.issued | 2015-11-01 | es_ES |
dc.identifier.issn | 0885-8950 | es_ES |
dc.identifier.uri | https:doi.org10.1109TPWRS.2014.2381360 | es_ES |
dc.description | Artículos en revistas | es_ES |
dc.description.abstract | es-ES | |
dc.description.abstract | Generating units, participating in the secondary frequency control of a control area, are usually spinning units already connected to the network and operating outside their range of optimal performance. This paper deals with an alternative method of providing secondary frequency control called Rapid-Start (RS). It consists in assigning a regulation band to several off-line units (RS units) which are capable of being started and connected rapidly, therefore allowing the online units to operate closer to their nominal power. As RS operation may have economic benefits, an appropriate algorithm to start up an RS unit needs to be developed. This paper proposes a methodology to evaluate, compare, and choose the most appropriate RS algorithm among the ones developed for a certain AGC control area. An optimization model provides a reference by determining the hypothetically ideal start-ups and shut-downs of RS units. In addition, the definition of performance indexes to evaluate, compare, and choose the different RS algorithms is proposed. The proposed methodology is illustrated for a secondary frequency control zone within the Spanish power system by using real data signals. | en-GB |
dc.format.mimetype | application/pdf | es_ES |
dc.language.iso | en-GB | es_ES |
dc.rights | es_ES | |
dc.rights.uri | es_ES | |
dc.source | Revista: IEEE Transactions on Power Systems, Periodo: 1, Volumen: online, Número: 6, Página inicial: 3130, Página final: 3138 | es_ES |
dc.subject.other | Instituto de Investigación Tecnológica (IIT) | es_ES |
dc.title | Performance evaluation of start-up decisions of rapid-start units for AGC | es_ES |
dc.type | info:eu-repo/semantics/article | es_ES |
dc.description.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.rights.accessRights | info:eu-repo/semantics/restrictedAccess | es_ES |
dc.keywords | es-ES | |
dc.keywords | Mixed-integer linear programming, Rapid-Start, secondary regulation. | en-GB |
Aparece en las colecciones: | Artículos |
Ficheros en este ítem:
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
IIT-15-049A.pdf | 1,19 MB | Adobe PDF | Visualizar/Abrir Request a copy |
Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.