Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/4962
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.authorAyala Santamaría, Pabloes-ES
dc.contributor.authorCantizano González, Alexises-ES
dc.contributor.authorGutiérrez Montes, Cándidoes-ES
dc.contributor.authorRein Soto-Yarritu, Guillermoes-ES
dc.date.accessioned2016-01-15T11:16:08Z-
dc.date.available2016-01-15T11:16:08Z-
dc.date.issued2013-10-01es_ES
dc.identifier.issn0378-7788es_ES
dc.identifier.urihttps://doi.org/10.1016/j.enbuild.2013.06.010es_ES
dc.descriptionArtículos en revistases_ES
dc.description.abstractThe use of computational fluid dynamics (CFD) as a tool for the design of smoke control systems and fire protection in large spaces has become more frequent as accuracy and computational speeds increase. In the present work Fire Dynamic Simulator (FDSv5) has been used to study two full-scale experiments conducted in Murcia (Spain) of 1.36 MW and 2.34 MW pool fires burning inside a 20 m cubic atrium under natural ventilation conditions. Different cartesian-grid approximations to the real geometry of the pyramidal roof have been investigated in order to assess the effect of stair stepping on the smoke layer and the temperature field. In general terms, good agreement between experiments and numerical simulations is found for all model roof geometries, especially far away from the fire source and the centreline. For example, at a height of 15 m, the temperature differences between all geometry approximations are lower than 10%. This shows that the cartesian-grid simplifications proposed here are a good choice and allow for saving some computational resources. In order to extend the results to different designs, the model has then been applied to study a range of 16 different atrium geometries, varying the area-to-height-squared ratio from 0.4 to 3.8. In addition, a comparison with simulation with a previous version of the code, FDSv4, shows that it predicts higher temperatures and slower ascends of the smoke layer than FDSv5, the difference being lower than 12% and 100 s respectively.es-ES
dc.description.abstractThe use of computational fluid dynamics (CFD) as a tool for the design of smoke control systems and fire protection in large spaces has become more frequent as accuracy and computational speeds increase. In the present work Fire Dynamic Simulator (FDSv5) has been used to study two full-scale experiments conducted in Murcia (Spain) of 1.36 MW and 2.34 MW pool fires burning inside a 20 m cubic atrium under natural ventilation conditions. Different cartesian-grid approximations to the real geometry of the pyramidal roof have been investigated in order to assess the effect of stair stepping on the smoke layer and the temperature field. In general terms, good agreement between experiments and numerical simulations is found for all model roof geometries, especially far away from the fire source and the centreline. For example, at a height of 15 m, the temperature differences between all geometry approximations are lower than 10%. This shows that the cartesian-grid simplifications proposed here are a good choice and allow for saving some computational resources. In order to extend the results to different designs, the model has then been applied to study a range of 16 different atrium geometries, varying the area-to-height-squared ratio from 0.4 to 3.8. In addition, a comparison with simulation with a previous version of the code, FDSv4, shows that it predicts higher temperatures and slower ascends of the smoke layer than FDSv5, the difference being lower than 12% and 100 s respectively.en-GB
dc.format.mimetypeapplication/octet-streames_ES
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.uries_ES
dc.sourceRevista: Energy and Buildings, Periodo: 1, Volumen: online, Número: , Página inicial: 382, Página final: 390es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titleInfluence of atrium roof geometries on the numerical predictions of fire tests under natural ventilation conditionses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.holderes_ES
dc.rights.accessRightsinfo:eu-repo/semantics/openAccesses_ES
dc.keywordsAtrium; Full scale fire tests; Smoke; CFD simulations; FDSv5; FDSv4es-ES
dc.keywordsAtrium; Full scale fire tests; Smoke; CFD simulations; FDSv5; FDSv4en-GB
Aparece en las colecciones: Artículos

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
ENB_2013_preprint.pdf7,92 MBAdobe PDFVisualizar/Abrir     Request a copy
IIT-13-071A_preview3,4 kBUnknownVisualizar/Abrir
IIT-13-071A_preview3,4 kBUnknownVisualizar/Abrir


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.