Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/5357
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.authorElices Vallejo, Albertoes-ES
dc.contributor.authorRouco Rodríguez, Luises-ES
dc.contributor.authorBourlès, Henries-ES
dc.contributor.authorMargotin, T.es-ES
dc.date.accessioned2016-01-15T11:19:57Z-
dc.date.available2016-01-15T11:19:57Z-
dc.date.issued2004-02-01es_ES
dc.identifier.issn0885-8950es_ES
dc.identifier.urihttps:doi.org10.1109TPWRS.2003.818730es_ES
dc.descriptionArtículos en revistases_ES
dc.description.abstractes-ES
dc.description.abstractThis paper presents a physical interpretation of two state feedback controllers for damping power system electromechanical oscillations. They have been developed by Electricité de France (EDF). The first one is called the desensitized four loop regulator (DFLR) and it is designed to damp local electromechanical oscillations. It is a robust controller which offers good performance despite the variations of the generator operating conditions. The second controller is called the extended desensitized four loop regulator (EDFLR) and it is designed to address both local and interarea oscillations. The physical interpretation is accomplished converting the state feedback scheme to the standard structure formed by an automatic voltage regulator (AVR) plus a power system stabilizer (PSS). Two widely used PSS design methods based on eigenvalue sensitivities and frequency response are reviewed to obtain the interpretation. The DFLR can be interpreted as a controller which provides the suitable phase compensation according to these two PSS design methods over a wider frequency range. The EDFLR can be interpreted as a controller which maximizes its robustness under uncertainties at both PSS output and the input of the plant.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.uries_ES
dc.sourceRevista: IEEE Transactions on Power Systems, Periodo: 1, Volumen: online, Número: 1, Página inicial: 436, Página final: 443es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titlePhysical interpretation of state feedback controllers to damp power system oscillationses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.accessRightsinfo:eu-repo/semantics/restrictedAccesses_ES
dc.keywordses-ES
dc.keywordsClassical PSS design, desensitization method, interarea oscillations, physical interpretation, robust controllers.en-GB
Aparece en las colecciones: Artículos