Por favor, use este identificador para citar o enlazar este ítem:
http://hdl.handle.net/11531/5686
Registro completo de metadatos
Campo DC | Valor | Lengua/Idioma |
---|---|---|
dc.contributor.author | Rivier Abbad, Juan Martín | es-ES |
dc.contributor.author | Rouco Rodríguez, Luis | es-ES |
dc.contributor.author | Castillo Campos, Juan Ignacio del | es-ES |
dc.contributor.author | Vindel, D. | es-ES |
dc.contributor.author | Vargas, Gregorio | es-ES |
dc.contributor.author | Herranz, A. | es-ES |
dc.date.accessioned | 2016-01-15T11:28:07Z | - |
dc.date.available | 2016-01-15T11:28:07Z | - |
dc.date.issued | 2003-08-25 | es_ES |
dc.identifier.uri | http://hdl.handle.net/11531/5686 | - |
dc.description | Capítulos en libros | es_ES |
dc.description.abstract | es-ES | |
dc.description.abstract | The usual lightning protection of high volt-age overhead lines is the usage of groundwires. In some cases, they cannot be used. This paper evaluates the effectiveness of different alternative protection schemes using surge arresters for a 132kV unshielded overhead line. The protection schemes are: a surge arrester at each conductor and tower, a surge arresters only at the central conductor and every tower (the configuration studied has the central conductor higher than lateral ones at therefore acts as a shield wire) and a surge arrester at each conductor and one out of two towers. The last two protective schemes are consid-ered due to economic reasons. Number of annual flashovers in a 100km line with the different protec-tion schemes is computed following IEEE recommen-dations. Direct, induced and back flashovers are con-sidered. Over-voltages are computed using the ATP software package, distinguishing between tower, cen-tral conductor and lateral conductor lightning strokes. Conclusions are presented about the effectiveness of each protective scheme. | en-GB |
dc.format.mimetype | application/pdf | es_ES |
dc.language.iso | en-GB | es_ES |
dc.publisher | Sin editorial (Delft, España) | es_ES |
dc.rights | es_ES | |
dc.rights.uri | es_ES | |
dc.source | Libro: XIIIth International Symposium on High Voltage Engineering (ISH 2003), Johan J. Smit Editor, Millpress (ISBN: 90-77017-79 8), pp. 137, Página inicial: , Página final: | es_ES |
dc.subject.other | Instituto de Investigación Tecnológica (IIT) | es_ES |
dc.title | Evaluation of lightning protection of unshielded 132kV overhead lines using surge arresters | es_ES |
dc.type | info:eu-repo/semantics/bookPart | es_ES |
dc.description.version | info:eu-repo/semantics/publishedVersion | es_ES |
dc.rights.accessRights | info:eu-repo/semantics/restrictedAccess | es_ES |
dc.keywords | es-ES | |
dc.keywords | No disponibleNot available | en-GB |
Aparece en las colecciones: | Artículos |
Ficheros en este ítem:
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
IIT-03-035A.pdf | 158,42 kB | Adobe PDF | Visualizar/Abrir Request a copy |
Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.