dc.description.abstractThis paper presents an algorithm for CT saturation detection based on the measurement of the power system source impedance seen from the relay location. The algorithm estimates this source impedance using a short-data window impedance-estimation algorithm. Samples are taken from the Current Transformer (CT) secondary current and bus-bar voltage. Following the changes of this impedance, the algorithm is able to detect a CT saturation. Due to its short data window, the algorithm is particularly adequate for fast tripping bus-bar differential relays.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.uries_ES
dc.sourceRevista: IEEE Transactions on Power Delivery, Periodo: 1, Volumen: online, Número: 4, Página inicial: 468, Página final: 472es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titleAn impedance-based CT saturation detection algorithm for bus-bar differential protectiones_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.accessRightsinfo:eu-repo/semantics/restrictedAccesses_ES
dc.keywordses-ES
dc.keywordsBus-bar protection, CT saturation detection, source impedance measurementen-GB