Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/87128
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.authorSanturino García, Paolaes-ES
dc.contributor.authorSigrist, Lukases-ES
dc.contributor.authorOrtega Manjavacas, Álvaroes-ES
dc.contributor.authorRenedo Anglada, Javieres-ES
dc.contributor.authorLobato Miguélez, Enriquees-ES
dc.date.accessioned2024-02-23T13:39:16Z-
dc.date.available2024-02-23T13:39:16Z-
dc.date.issued2022-10-01es_ES
dc.identifier.issn0378-7796es_ES
dc.identifier.urihttps:doi.org10.1016j.epsr.2022.108423es_ES
dc.descriptionArtículos en revistases_ES
dc.description.abstractes-ES
dc.description.abstractUnder-frequency load shedding (UFLS) is considered a fundamental protection tool against power imbalances in electrical grids, particularly in small island systems. However, load shedding entails a delicate compromise between guaranteeing the stability of the system and disconnecting the lowest amount of load to achieve it. Fast-responding converter-interfaced energy storage systems (ESSs) can help improve such a compromise. In this regard, this paper proposes a methodology for the coordinated design of under-frequency load shedding (UFLS) and fast-responding converter-interfaced energy storage systems (ESSs). UFLS parameters include thresholds for frequency and its rate-of-change, and time settings of each step. ESS control parameters comprise, among others, the emulated inertia and the droop. The proposed coordinated methodology is applied to a real Spanish island power system with a 4 MW5.6 kWh ultracapacitor (UC). Results show that the proposed methodology is able to significantly reduce the total amount of load shed with respect to the currently implemented UFLS settings and UC control parameters.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.uries_ES
dc.sourceRevista: Electric Power Systems Research, Periodo: 1, Volumen: online, Número: , Página inicial: 108423-1, Página final: 108423-8es_ES
dc.subject.otherInstituto de Investigación Tecnológica (IIT)es_ES
dc.titleOptimal coordinated design of under-frequency load shedding and energy storage systemses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.description.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.rights.accessRightsinfo:eu-repo/semantics/restrictedAccesses_ES
dc.keywordses-ES
dc.keywordsFrequency stability; Under-frequency load shedding; Energy storage systems; Ultracapacitors; Island gridsen-GB
Aparece en las colecciones: Artículos

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
IIT-22-133R.pdf1,36 MBAdobe PDFVisualizar/Abrir     Request a copy


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.