Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/11531/88258
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorTroncia, Matteoes-ES
dc.contributor.authorCarnicero Príncipe, Davides-ES
dc.contributor.otherUniversidad Pontificia Comillas, Escuela Técnica Superior de Ingeniería (ICAI)es_ES
dc.date.accessioned2024-04-19T10:07:53Z-
dc.date.available2024-04-19T10:07:53Z-
dc.date.issued2024es_ES
dc.identifier.urihttp://hdl.handle.net/11531/88258-
dc.descriptionMaster in Smart Gridses_ES
dc.description.abstractLa tesis titulada "Evaluación de la Viabilidad de Sustituir Sensores Físicos por Servicios Meteorológicos para DLR en Sistemas Eléctricos" presenta una investigación detallada sobre el potencial de reemplazar sensores físicos de campo con datos meteorológicos de terceros para la capacidad dinámica de líneas (DLR) en redes de distribución eléctrica. La investigación se contextualiza dentro del marco operativo de Iberdrola, una importante empresa global de energía, y se centra en las líneas de distribución de la compañía. El estudio evalúa a varios proveedores de servicios meteorológicos, incluyendo Copernicus, MeteoFlow y Open-Meteo, comparando la precisión de sus datos con las medidas de sensores recogidas de seis líneas eléctricas diferentes. La investigación incluye el desarrollo de herramientas basadas en Python para normalizar los datos de las líneas eléctricas, lo que permite una recopilación precisa de los datos meteorológicos relevantes y el cálculo exacto de DLR para cada tramo de las líneas de distribución. El análisis emplea técnicas estadísticas avanzadas para evaluar la dispersión, correlación, métricas de error e incertidumbre de las estimaciones meteorológicas. Este proceso es esencial para determinar si estas estimaciones pueden sustituir eficazmente a los sensores físicos, particularmente en términos de velocidad y dirección del viento, variables críticas para los cálculos precisos de DLR. La investigación también incorpora un análisis de sensibilidad global y regional de las variables meteorológicas involucradas, utilizando estándares como el IEEE-738 y el CIGRE-TB 601, y explora metodologías para predecir el DLR basándose en pronósticos meteorológicos a corto plazo. Los hallazgos indican que, si bien los datos meteorológicos pueden potencialmente reemplazar a los sensores de temperatura y radiación solar, la precisión de los datos de viento sigue siendo inconsistente, lo que plantea desafíos para el cálculo fiable de DLR. La tesis concluye que un enfoque híbrido—que integre tanto la modelización meteorológica como las medidas físicas—puede mejorar la fiabilidad de la red y la eficiencia operativa, aunque la sustitución completa de los sensores físicos aún no es factible en todos los escenarios. Este estudio exhaustivo proporciona conocimientos críticos y recomendaciones prácticas para Iberdrola y contribuye al campo más amplio de la gestión de redes inteligentes, explorando soluciones rentables y escalables para la implementación de DLR.es-ES
dc.description.abstractThe thesis titled "Evaluating the Feasibility of Replacing Physical Sensors with Meteorological Services for DLR in Power Systems" presents a detailed investigation into the potential of replacing physical field sensors with third-party meteorological data for Dynamic Line Rating (DLR) in power distribution networks. The research is contextualized within the operational framework of Iberdrola, a major global power utility, and focuses on the company’s distribution lines. The study evaluates various meteorological service providers, including Copernicus, MeteoFlow, and Open-Meteo, by comparing the accuracy of their data against sensor measurements collected from six different power lines. The research involves the development of Python-based tools for normalizing electrical line data, enabling accurate collection of relevant meteorological data and the precise calculation of DLR for each span of the distribution lines. The analysis employs advanced statistical techniques to assess the dispersion, correlation, error metrics, and uncertainty of meteorological estimates. This process is essential to determine whether these estimates can effectively replace physical sensors, particularly in terms of wind speed and direction—variables critical to accurate DLR calculations. The research also incorporates a global and regional sensitivity analysis of the meteorological variables involved, utilizing standards such as IEEE-738 and CIGRE-TB 601, and explores methodologies for predicting DLR based on short-term weather forecasts. The findings indicate that while meteorological data can potentially replace temperature and solar radiation sensors, the accuracy of wind data remains inconsistent, posing challenges for reliable DLR calculation. The thesis concludes that a hybrid approach—integrating both meteorological modeling and physical measurements—can improve grid reliability and operational efficiency, although complete replacement of physical sensors is not yet feasible across all scenarios. This comprehensive study provides critical insights and practical recommendations for Iberdrola and contributes to the broader field of smart grid management by exploring cost-effective and scalable solutions for DLR implementation.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.rightsAttribution-NonCommercial-NoDerivs 3.0 United Stateses_ES
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/us/es_ES
dc.subject.otherM8Ees_ES
dc.titleDynamic Line Rating (DLR) system without DLR deviceses_ES
dc.typeinfo:eu-repo/semantics/masterThesises_ES
dc.rights.accessRightsinfo:eu-repo/semantics/openAccesses_ES
dc.keywordsSmart Grids, Dynamic Line Rating, servicios meteorológicos, sustitución de sensores, análisis de incertidumbre, capacidad líneas,es-ES
dc.keywordsSmart Grids, Dynamic Line Rating, Meteorological Services, Sensor Replacement, Sensitivity Analysis, Power Grid Reliability, Uncertainty Analysisen-GB
Aparece en las colecciones: TFG, TFM (temporales)

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
TFM - Carnicero Principe David.pdfTrabajo Fin de Máster5,5 MBAdobe PDFVisualizar/Abrir
AnexoI_signedMT.pdfAutorización232,56 kBAdobe PDFVisualizar/Abrir


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.