Resumen
This paper uses eigenvalue sensitivities to address the coordinated design of multiple power oscillation damping (POD) controllers of an HVDC-VSC link. Namely, POD controllers modulating the active and reactive power of each pole’s converter are designed. This paper shows the feasibility of applying such an approach to a large-scale power system and the challenges encountered. Moreover, the coordinated design method based on eigenvalue sensitivities has been extended to design POD controllers valid for several operating conditions. In particular, N-1 conditions in the parallel AC lines are considered. The performance of the proposed controller designs is checked in the time and frequency domains.
Coordinated tuning of multiple power oscillation damping controllers of HVDC links: Application to a large-scale power system