TDSF-Based Evaluation of Transformer Interactions with VCB, Cable Length, and Neutral Grounding

Thumbnail
Ver/
IIT-25-408C.pdf (1.379Mb)
Autor
Álvarez-Mariño, Casimiro
López Fernández, Xosé Manuel
Popov, Marjan
Rouco Rodríguez, Luis
Estado
info:eu-repo/semantics/draft
Metadatos
Mostrar el registro completo del ítem
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Resumen
 
 
This paper presents a TDSF-based evaluation of dielectric severity in transformer windings, focusing on transient overvoltages induced by cable–transformer interactions during vacuum circuit breaker (VCB) closing. Unlike prior approaches limited to terminal voltages, this study investigates the highest both spatial and temporal dielectric stress across all combinations of winding nodes and their reference to ground. A hybrid white–black box transformer model implemented in ATP/EMTP is presented and used for high-frequency transient analysis within the transformer. Three case studies on a 50 MVA single-phase, multi-winding transformer validate the model and assess the impact of cable length and neutral grounding resistance. Results show that certain cable lengths increase dielectric stress due to resonance effects, though without exceeding critical thresholds. In contrast, grounding conditions at the LV terminal significantly affect the vulnerability of the winding neutral point. The findings underscore the effectiveness of TDSF-based evaluation in identifying critical stress locations and supporting insulation coordination strategies.
 
URI
http://hdl.handle.net/11531/108904
TDSF-Based Evaluation of Transformer Interactions with VCB, Cable Length, and Neutral Grounding
Palabras Clave

Dielectric severity factor, Dielectric tests, Insulation system, High frequency modelling, Network studies Power transformers, Time Domain Severity Factor, Switching operation, Vacuum circuit breaker.
Colecciones
  • Documentos de Trabajo

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contacto | Sugerencias
 

 

Búsqueda semántica (CKH Explorer)


Listar

Todo DSpaceComunidades & ColeccionesPor fecha de publicaciónAutoresTítulosMateriasPor DirectorPor tipoEsta colecciónPor fecha de publicaciónAutoresTítulosMateriasPor DirectorPor tipo

Mi cuenta

AccederRegistro

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contacto | Sugerencias