TDSF-Based Evaluation of Transformer Interactions with VCB, Cable Length, and Neutral Grounding

Thumbnail
View/Open
IIT-25-408C.pdf (1.379Mb)
Author
Álvarez-Mariño, Casimiro
López Fernández, Xosé Manuel
Popov, Marjan
Rouco Rodríguez, Luis
Estado
info:eu-repo/semantics/draft
Metadata
Show full item record
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Abstract
 
 
This paper presents a TDSF-based evaluation of dielectric severity in transformer windings, focusing on transient overvoltages induced by cable–transformer interactions during vacuum circuit breaker (VCB) closing. Unlike prior approaches limited to terminal voltages, this study investigates the highest both spatial and temporal dielectric stress across all combinations of winding nodes and their reference to ground. A hybrid white–black box transformer model implemented in ATP/EMTP is presented and used for high-frequency transient analysis within the transformer. Three case studies on a 50 MVA single-phase, multi-winding transformer validate the model and assess the impact of cable length and neutral grounding resistance. Results show that certain cable lengths increase dielectric stress due to resonance effects, though without exceeding critical thresholds. In contrast, grounding conditions at the LV terminal significantly affect the vulnerability of the winding neutral point. The findings underscore the effectiveness of TDSF-based evaluation in identifying critical stress locations and supporting insulation coordination strategies.
 
URI
http://hdl.handle.net/11531/108904
TDSF-Based Evaluation of Transformer Interactions with VCB, Cable Length, and Neutral Grounding
Palabras Clave

Dielectric severity factor, Dielectric tests, Insulation system, High frequency modelling, Network studies Power transformers, Time Domain Severity Factor, Switching operation, Vacuum circuit breaker.
Collections
  • Documentos de Trabajo

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback
 

 

Búsqueda semántica (CKH Explorer)


Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_typeThis CollectionBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_type

My Account

LoginRegister

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback