dc.description.abstractes-ES
dc.description.abstractA new Voltage Sag Generator (VSG) to test synchronous generators Fault Ride Through (FRT) capability as required by grid codes is proposed. This VSG consists of an electronically controlled tap changer transformer that takes into account the technological constraints of synchronous generators. A 10 kVA prototype has been assembled and tested. It has been demonstrated that this VSG reproduces faithfully the interactions between the generator and the grid during voltage sags.en-GB
dc.format.mimetypeapplication/pdfes_ES
dc.language.isoen-GBes_ES
dc.rightses_ES
dc.rights.uries_ES
dc.titleImplementation of a voltage sag generator for synchronous generator testses_ES
dc.typeinfo:eu-repo/semantics/workingPaperes_ES
dc.description.versioninfo:eu-repo/semantics/draftes_ES
dc.rights.accessRightsinfo:eu-repo/semantics/restrictedAccesses_ES
dc.keywordses-ES
dc.keywordsElectronic Tap Changer Transformer, Voltage Sag Generator, Transient Stability, Fault Ride Through, Grid Codes.en-GB