Influence of the phase-locked loop on the design of microgrids formed by diesel generators and grid-forming converters

Thumbnail
Ver/
IIT-21-032A.pdf (1.758Mb)
Autor
Morán Río, Diana Patricia
Roldan Perez, Javier
Prodanovic, Milan
García Cerrada, Aurelio
Estado
info:eu-repo/semantics/draft
Metadatos
Mostrar el registro completo del ítem
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Resumen
 
 
In recent years, Microgrids (MGs) with renewable energy sources, diesel gen-sets and droop-controlled converters have been increasingly used to guarantee the continuity of power supply in remote areas. Renewable energy sources have been typically connected to MGs by using an electronic converter that features the two controllers: a current-control loop and a phaselocked loop (PLL). Stability issues related to the PLLs application in electrical grids have already been addressed in the literature, however, dynamic interactions in MGs caused by PLLs have not been sufficiently explored. In this paper, a MG that includes a grid-feeding voltage source converter and a grid-forming device (diesel gen-set or converter) is studied. All network elements are modelled analytically and the eigenvalue and participation-factor analyses are used to analyse the interactions between the devices.It is demonstrated that MGs formed by diesel gen-sets have reduced stability limits. Also, it is shown that stability margins of MGs formed by droop-controlled converters can be improved by changing the control parameters (e.g. PLL and internal controllers bandwidths). The main findings and conclusions are summarised and presented as a practical MG design guide.Theoretical results are validated in a lab environment comprising two 15 kW converters and one 75 kW grid emulator.
 
URI
http://hdl.handle.net/11531/56148
Influence of the phase-locked loop on the design of microgrids formed by diesel generators and grid-forming converters
Palabras Clave

Microgrid, Phase-Locked Loop, Current Control, Diesel Generator, Droop Control, Small-Signal Analysis.
Colecciones
  • Documentos de Trabajo

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contacto | Sugerencias
 

 

Búsqueda semántica (CKH Explorer)


Listar

Todo DSpaceComunidades & ColeccionesPor fecha de publicaciónAutoresTítulosMateriasPor DirectorPor tipoEsta colecciónPor fecha de publicaciónAutoresTítulosMateriasPor DirectorPor tipo

Mi cuenta

AccederRegistro

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contacto | Sugerencias