Analysis of Grid-forming/following STATCOMs and Synchronous Compensators for Grid-following IBRs stability

Thumbnail
View/Open
IIT-26-059WP.pdf (780.4Kb)
Author
Suárez Porras, Jorge
Fernández Bernal, Fidel
Rouco Rodríguez, Luis
Avila Martinez, Regulo Enrique
Tomás Martín, Andrés
García Cerrada, Aurelio
Bueno Peña, Emilio José
Estado
info:eu-repo/semantics/draft
Metadata
Show full item record
Mostrar METS del ítem
Ver registro en CKH

Refworks Export

Abstract
This paper investigates how different compensating devices can enhance the small-signal stability of the system by means of the phase-locked loop (PLL) in inverter-based resources (IBRs) operating in grid-following mode. Three technologies are compared: synchronous compensator (SC), STATCOM operated in grid-forming (GFr) mode, and static synchronous compensator (STATCOM) operated in grid-following (GFl) mode. A systematic control design procedure is proposed for the GFr STATCOM, combining pole-placement for the inner current loop and phase margin design for the outer voltage loop. The study relies on small-signal eigenvalue analysis and time-domain simulations under transient disturbances. To provide a representative case study, a doubly-fed induction generator (DFIG) is used as the IBR device model due to its complex dynamics and direct coupling between the machine and the grid. Results confirm that both SC and GFr STATCOM significantly improve the system stability, whereas GFl STATCOM provides negligible benefits.
 
This paper investigates how different compensating devices can enhance the small-signal stability of the system by means of the phase-locked loop (PLL) in inverter-based resources (IBRs) operating in grid-following mode. Three technologies are compared: synchronous compensator (SC), STATCOM operated in grid-forming (GFr) mode, and static synchronous compensator (STATCOM) operated in grid-following (GFl) mode. A systematic control design procedure is proposed for the GFr STATCOM, combining pole-placement for the inner current loop and phase margin design for the outer voltage loop. The study relies on small-signal eigenvalue analysis and time-domain simulations under transient disturbances. To provide a representative case study, a doubly-fed induction generator (DFIG) is used as the IBR device model due to its complex dynamics and direct coupling between the machine and the grid. Results confirm that both SC and GFr STATCOM significantly improve the system stability, whereas GFl STATCOM provides negligible benefits.
 
URI
http://hdl.handle.net/11531/108844
Analysis of Grid-forming/following STATCOMs and Synchronous Compensators for Grid-following IBRs stability
Palabras Clave
Synchronous compensator, synchronous condenser, short-circuit ratio, grid-forming, grid-following, doublyfed induction generator, reactive power, inverter-based resources, PLL stability.
Synchronous compensator, synchronous condenser, short-circuit ratio, grid-forming, grid-following, doublyfed induction generator, reactive power, inverter-based resources, PLL stability.
Collections
  • Documentos de Trabajo

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback
 

 

Búsqueda semántica (CKH Explorer)


Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_typeThis CollectionBy Issue DateAuthorsTitlesSubjectsxmlui.ArtifactBrowser.Navigation.browse_advisorxmlui.ArtifactBrowser.Navigation.browse_type

My Account

LoginRegister

Repositorio de la Universidad Pontificia Comillas copyright © 2015  Desarrollado con DSpace Software
Contact Us | Send Feedback